Chapter 1
14 Concord Express Installation Instructions
Figure 7: Installing and connecting the HIM in the Concord Express
Connecting Detection Devices to Panel Zone Inputs
The panel comes with six factory programmed onboard hardwire zones (see
Accessory Modules Menuon page 60 for factory settings). Zone inputs 1
through 6 are supervised using a 2k-ohm, end-of-line resistor (included with
panel) at the last device on the circuit.
Note: Install an end-of-line resistor on all unused, factory programmed, onboard
panel zones.
All six zones accept either normally open (N/O) or normally closed (N/C)
detection devices (see Figure 8 on page 15).
The maximum loop resistance for each zone input is 300 ohms, plus the 2k end-
of-line (EOL) resistor.
Connecting Intrusion Detection Devices
Figure 8 on page 15 shows the typical wiring for N/C and N/O door/window
intrusion detection.